Watlow Series SD6 PID Controller with DeviceNet Addendum Manuel d'utilisateur Page 30

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 32
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 29
Watlow Series SD6 PID with DeviceNet 30
Class Services:
0x0E GET ATTRIBUTE SINGLE
Instance Services:
0x0E GET ATTRIBUTE SINGLE
0x10 SET ATTRIBUTE SINGLE
NOTE: All successful Explicit Message
Responses from a SET service will contain no
data. The response will be a two-byte message
containing the requester’s MAC ID and Service
Code (with R/R bit set).
Profile Program Object
Class Code: 6Ahex
Profile Program Object
The Profile Program Object provides access to parameters
that contain profile programs.
Table 37. Profile Program Object Revision History
Revision Description
01 Initial Release
Attribute # Access Rule Name DeviceNet
Data Type
Description of Attribute Semantics of Values
113 Get Hours Remaining UINT Indicates number of hours
remaining in the step cur-
rently running
0 to 99
114 Get Minutes Remaining UINT Indicates number of minutes
remaining in the step cur-
rently running
0 to 59
115 Get Seconds Remaining UINT Indicates number of seconds
remaining in the step cur-
rently running
0 to 59
116 Get Ramp Rate UDINT Rate at which the profile
changes in degrees or units
per minute
0.0 to 9999.9 (*1000)
117 Get Event Output 1 sta-
tus
BOOLEAN Indicates Event Output 1 sta-
tus
(0)- OFF
(1)- ON
118 Get Event Output 2 sta-
tus
BOOLEAN Indicates Event Output 2 sta-
tus
(0)- OFF
(1)- ON
119 Get Wait-for Process
Value
DINT Profile clock waits until the
process value matches the
Wait-for value and continues
with the step
(Splo) to (sphi)
120 Get Elapsed Jump
Count
UDINT Number of times the profile
has been through the Jump
Loop Step
0 to 9999 (*1000)
121 Get Failed File Number UINT Indicates the file number that
failed the Pre-Run check
1 to 4
122 Get Failed Step Number UINT Indicates the step number
that failed the Pre-Run check
1 to 10
123 Get/Set Comms
Temperature Units
BOOLEAN This register determines the
units of measure for temper-
ature values during
DeviceNet communication
(0)- Fahrenheit (default)
(1)- Celsius