Watlow ANASCAN Manuel d'utilisateur Page 40

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 62
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 39
32 ANASCAN Users Guide
C H A N N E L S E T U P
The diagram below shows the different alarm types.
High and Low
Deviation
Alarms
O = OFF
L =
Latched(Default)
U = Unlatched
See above descriptions.
High and Low
Deviation Alarm
Outputs
N, 1 to 34
default = NONE
N = NONE
Alarm Deadband 0 to 255
default = 0
See figure below.
Alarm Deviation 0 to 255
default = 25
See figure below.
Alarm Delay 0 to 255
default = 0
See figure below.
Field Name Selections Notes
Hi
g
h Alarm Limit
Setpoint
Low Alarm Limit
SP + Deviation
SP - Deviation
}
Deadband
}
Deadband
}
Deadband
}
Deadband
Hi
g
h deviation alarm on
Hi
g
h deviation alarm off
Low deviation alarm on
Low deviation alarm off
Hi
g
h process alarm off
Hi
g
h process alarm on
Low process alarm on
Low process alarm off