Setup
CLS Users Guide 67
Keyboard Lock Status
Use this menu to lock the front panel operator function keys
Change
SP, Man/Auto
, and
Ramp/Soak
so that pressing these keys has no
effect. If you want to use these functions, turn off the Keyboard Lock.
Selectable values:
On or Off.
Power-Up Output Status
Use this menu to set the initial power-up state of the control outputs to
Off or Memory. If you choose Off, all control outputs are initially set to
Manual mode at 0% output level. If you choose Memory, the outputs are
restored to the last output state stored in memory.
WARNING
Do not set the CLS to start from memory if a memory-
based restart is unsafe for your process.
Selectable values:
Off or Memory.
Controller Address
Use this menu to set the CLS address. The controller address is used for
multiple controller communications on a single 485 cable, so each CLS
must have a different address. Begin with address 1 for the first
controller and assign each subsequent controller the next higher address.
Selectable values:
1-32.
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
KEYBOARD LOCK
STATUS ? OFF
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
POWER UP OUTPUT
STATUS ? OFF
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
CONTROLLER
ADDRESS ? 1