Watlow 12LS Controller Manuel d'utilisateur Page 80

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 111
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 79
4-47
ENTER Open the selected profile for editing. The display advances to the
Copy Profile Menu.
BACK Return to SETUP R/S PROFILE ? prompt.
NO Select the default profile for editing. The display advances to Copy
Another Profile.
BACK Return to the SETUP R/S PROFILE ? prompt.
4.7.2 COPY ANOTHER PROFILE
This menu allows copying of another profile into the profile currently selected. This shortcut
method is useful when the majority of a profile is similar to one that already exists.
As a default choice the initial prompt offers to copy the profile immediately preceding the current
profile (or L if editing profile A) but any of the other profiles may be selected.
|---------------|
Display: ¦ COPY SETUP ¦
¦ FROM PROFILE ?¦
|---------------|
The ? flashes.
x is the profile to be copied [A-L].
YES Select a profile to copy from.
Lower display
COPY = x
UP/DOWN Select profile to copy.
ENTER Copy profile contents. Display advances
to Edit Tolerance Alarm Time.
BACK Return to SETUP R/S PROFILE? prompt.
NO Skip profile copying menu. Display advances
to Edit Tolerance Alarm Time.
BACK Return to SETUP R/S PROFILE? prompt.
4.7.3 EDIT TOLERANCE ALARM TIME
With this menu the maximum out-of-tolerance time for any segment within the profile may be set.
Units are either Hours:Minutes or Minutes:Seconds depending on the global time base selected.
Values from 00:01 to 99:59 may be entered. The default is 1:00.
Vue de la page 79
1 2 ... 75 76 77 78 79 80 81 82 83 84 85 ... 110 111

Commentaires sur ces manuels

Pas de commentaire