4-48
When any segment is out of tolerance for a period greater than the Tolerance Time entered, a
tolerance alarm is generated. A tolerance alarm activates the global annunciator output and
displays a 'T' in the alarm status position on the display.
|------------------|
Display: ¦ x OUT-OF-TOLRNCE ¦
¦ ALARM TIME:?hh:mm¦
|------------------|
x is the profile designator [A-L].
The ? flashes.
hh:mm is the current out-of-tolerance time limit.
YES Edit the tolerance limit time.
Lower display T =hh:mm
UP/DOWN Adjust time.
ENTER Store the new setting. The display advances to Edit Ready Setpoint.
BACK Return to the SETUP R/S PROFILE? prompt.
NO Leave tolerance time value as it is. The display advances to Edit Ready
Setpoint.
BACK Return to the SETUP R/S PROFILE? prompt.
4.7.4 EDIT READY SETPOINT
This menu allows editing of the ready state setpoint. This is the setpoint that will be loaded
whenever the profile is in the START (or ready) state.
A profile enters START mode whenever it is first assigned to a loop. It also returns to START
mode after completing execution.
The ready setpoint provides a starting point at which segment 1 will begin.
|----------------|
Display: ¦ x READY SEGMENT¦
¦ SETPOINT ? yyyy¦
|----------------|
The ? is flashing.
x is the profile designator [A-L].
yyyy is the current ready setpoint.
YES Change the ready state setpoint.
Lower display SP =yyyy
UP/DOWN Adjust setpoint.