24 CAS Users Guide
Installation
Scaling Values
For linear mVdc, Vdc, and mAdc ranges, use 0.1% tolerance resistors.
Larger tolerances may cause significant errors. Correct any errors due to
resistor tolerance with built-in linear scaling. You can also install other
components (like capacitors) for signal conditioning; please consult
Watlow Anafaze for more information.
The next table shows scaling resistor values.
Input Range RC RD
All T/C, 0-60 mV DC Jumper
0-10 mA DC
0-20 mA DC
Jumper
Jumper
6.0 ohms
3.0 ohms
0-100 mV
0-500 mV
499 ohms
5.49 Kohms
750 ohms
750 ohms
0-1 VDC
0-5 VDC
0-10 VDC
0-12 VDC
6.91 Kohms
39.2 Kohms
49.9 Kohms
84.5 Kohms
422.0 ohms
475.0 ohms
301.0 ohms
422.0 ohms