Setup
CAS Users Guide 53
The PV (Process Variable) range for the scaled input is between the PV
values that correspond to the 0% and 100% input readings. For the pulse
input, it is between the 0 Hz and 2000 Hz readings. This PV range
defines the limits for the setpoint and alarms, as shown here.
NOTE
For example linear scaling calculations, see Appendix: Linear
Scaling.
Process
Variable
InputR eading
0 PSI
0%
0mV
0Hz
100%
60 m V
2000 H z
HiPV
}
Linearinputtype
}Pulse inputtyp
e
Lo
Rdg
Lo PV
Range