RTD
Field Calibration Procedure
Figure
38
-
Decade Resistance
Box-to-Series 920
Connection Diagram
Equipment Required
l
100 ohm precision decade resistance box with 0.00 ohms resolution.
l
4-1/2
digit, digital voltmeter (DVM).
Setup and Calibration
1
NOTE:
Before calibration on an installed control, make sure all data and
parame-
ters are documented.
1.
Connect the precision decade box to #1 ,
#2,
and
#3
of the Series 920
terminal
strip as shown in the figure below.
Series
920
Terminal Strip
@)(sJ(g;
General Radio Model
#1433-T
2.
Connect AC line voltage,
L1
to
#17,
L2
to
#20,
ground to
#21.
3.
Set DIP switch
#8
ON. Apply power to the Series 920 and allow it to warm
up for
15
minutes. The unit should be in the TEST mode.
4.
Using the MODE key, advance until the IN
X
parameter appears in the
alphanumeric display. Using the UP/DOWN keys, advance to your correct
RTD
input type. Press the ENTER key.
5.
Connect DVM common to TP84 and DVM positive to TP36 on the
AOO7-
1703 circuit board. Located on the top side behind the center chassis
support.
DVM should be set up for DC volts, and in a range capable of
displaying 32.00 millivolts
±
1
0mV.