Watlow Series SD 60 Chapter 11 Factory
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
[O;ty1]
[O.ty1]
Output 1 Type
Displays the hardware type for
Output 1.
[nonE] none (0)
[~~DC] DC/open collect. (1)
[rLAY] mech. relay (2)
[~SSr] solid-state relay (3)
[Proc] process (4)
[nonE]
none (0)
202 R Always active.
[O;ty2]
[O.ty2]
Output 2 Type
Displays the hardware type for
Output 2.
[nonE] none (0)
[~~DC] DC/open collect. (1)
[rLAY] mech. relay (2)
[~SSr] solid-state relay (3)
[COM] communications (5)
[nonE]
none (0)
203 R Always active.
[O;ty3]
[O.ty3]
Output 3 Type
Displays the hardware type for
Output 3.
[nonE] none (0)
[~~DC] DC/open collect. (1)
[rLAY] mech. relay (2)
[~SSr] solid-state relay (3)
[Proc] process (4)
[nonE]
none (0)
204 R Always active.
[`S;id]
[ S.id]
Software ID
Displays the software ID number.
0 to 9999 NA 10 R Always active.
[S;UEr]
[S.VEr]
Software Version
Displays the firmware revision.
0.00 to 99.99 NA 11 R Always active.
[S;bLd]
[S.bLd]
Software Build Number
Displays the software build num-
ber.
0 to 9999 Build Number NA 13 R Always active.
[PWr]
[PWr]
Power Type
Displays the type of input power.
[~~AC] high voltage
[LOW] low voltage
NA *NA Always active.
[`Sn-]
[ Sn-]
Serial Number 1
Displays the first four characters
of the serial number.
0 to 9999 NA 7,8 R Always active.
[`Sn_]
[ Sn_]
Serial Number 2
Displays the last four characters
of the serial number.
0 to 9999 NA 7,8 R Always active.
Restoring Factory Calibration
Press the Up ¿ and Down ¯ keys together for six seconds until [FAct] appears in the upper display and
[PagE] appears in the lower display.
• Press the Advance Key to step through the parameters until the [rESt] appears.
Use the Up Key ¿ to select [`yES] in the upper display.
Press the Infinity Key ˆ to exit the Factory Page.
Calibration information for the Series SD controllers is available in pdf format. Go to www.watlow.
com > Literature > Product User Manuals and search on Series SD Calibration Manual.
Vue de la page 61