LogicPro Users Guide Chapter 12: Function Blocks
Doc.# 28002-00 Rev 3.00 Watlow Anafaze 213
CPC400_Digital_Out
The CPC400_Digital_Out allows a logic program to access the state
of each of the digital outputs.
To read or set a digital output with a logic program variable:
1. Open the Add Program/Resource Variable dialog box.
2. Enter a unique variable Name.
3. Select BOOL from the Type list.
4. Select Input or Output by clicking the corresponding check
box.
5. Select CPC400_Digital_Out from the IO Driver list.
6. In the IO Physical Address field, enter the digital output
number (1 to 34).
7. Click [OK]
CPC400_Digital_Out Addressing Example
To create a variable named My_Dig_Out that sets the value of
the 23rd output on a CPC400, set the options in the Add
Program/Resource Variable dialog box as illustrated
below.