Watlow EZ-ZONE
®
RML Module • 33 • Chapter 3 Operations Page
RM Limit Module • Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
No Dis-
play
Digital Input (1 to 6 and 9)
Source Error
View the state of this out-
put.
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Calibration Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
None 1878
[offset 30]
0x6A (106)
1 to 9
0x0F (15)
- - - - 6015 uint
R
No Dis-
play
Digital Output (1 to 8)
Output State
View the state of this out-
put.
Off (62)
On (63)
- - - - 1862
[offset 30]
0x6A (106)
1 to 8
7
- - - - 6007 uint
R
[`ACt]
[oPEr]
Action Menu
[`Ei;S]
[ Ei.S]
Action (1 to 16)
Event Input Status
View this input state.
[`off] Off (62)
[``on] On (63)
2218
[offset 20]
0x6E (110)
1 to 0x10
(16)
5
140 10005 uint
R
No Dis-
play
Function Key (1)
Function Key State
View current state of func-
tion key 1.
Off (62)
On (63)
- - - - - - - - - - - - - - - - 3024 uint
R
No Dis-
play
Function Key (2)
Function Key State
View current state of func-
tion key 2..
Off (62)
On (63)
- - - - - - - - - - - - - - - - 3030 uint
R
[LiM]
[oPEr]
Limit Menu
[`LL;S]
[ LL.S]
Limit (1 to 12)
Low Set Point
Set the low process value
that will trigger the limit.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
1494
[offset 30]
0x70 (112)
1 to 0xC
(12)
3
38 12003 float
RWES
[`Lh;S]
[ Lh.S]
Limit (1 to 12)
High Set Point
Set the high process value
that will trigger the limit.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
1496
[offset 30]
0x70 (112)
1 to 0xC
(12)
4
39 12004 float
RWES
[`l;Cr]
[L.Cr]
Limit (1 to 12)
Clear Request
Clear limit once limit con-
dition is cleared.
Clear (129)
Ignore (204)
Ignore
- - - - - - - - - - - - 12014 uint
R
[`l;st]
[L.St]
Limit (1 to 12)
Status
Reflects whether or not
the limit is in a safe or
failed mode..
Fail (32)
Safe (1667)
- - - -
1514
[offset 30]
0x70 (112)
1 to 0xC
(12)
0x0D (13)
- - - - 12013 uint
R
No Dis-
play
Limit (1 to 12)
State
Current state of limit.
Off (62)
None (61)
Limit High (51)
Limit Low (52)
Error (225)
- - - -
1500
[offset 30]
0x70 (112)
1 to 0xC
(12)
6
- - - - 12006 uint
R
Note: Some values will be rounded off to fit in the four-character display. Full values
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set