Watlow EZ-ZONE
®
RML Module • 59 • Chapter 4 Setup Page
RM Limit Module • Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`LgC]
[`Set]
Logic Menu
[``Fn]
[ Fn]
Logic (1 to 16)
Function
Set the operator that will
be used to compare the
sources.
[`oFF] Off (62)
[`And] And (1426)
[nAnd] Nand (1427)
[``or] Or (1442)
[`nor] Nor (1443)
[```E] Equal To (1437)
[``nE] Not Equal To (1438)
[`LAt] Latch (1444)
[rs;ff] Flip-Flop (1693)
Off 4694
[offset 80]
0x7F (127)
1 to 16
0x21 (33)
235 27033 uint
RWES
[SFn;A]
[SFn.A]
Logic (1 to 16)
Source Function A
Set the type of function
that will be used for this
source.
[[nonE] None (61)
[ALM] Alarm Reset (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out A
(233)
[Ent;b] Profile Event Out B
(234)
[Ent;C] Profile Event Out C
(235)
[Ent;d] Profile Event Out D
(236)
[Ent;E] Profile Event Out E
(247)
[Ent;F] Profile Event Out F
(248)
[Ent;g] Profile Event Out G
(249)
[Ent;h] Profile Event Out H
(250)
[`FUn] Function Key (1001)
[lim] Limit (126)
[`lgC] Logic (239)
[SoF;1] Special Function Out-
put 1 (1532)
[SoF;2] Special Function Out-
put 2 (1533)
[SoF;3] Special Function Out-
put 3 (1534)
[SoF;4] Special Function Out-
put 4 (1535)
[tMr] Timer (244)
[`uAr] Variable (245))
None 4630
[offset 80]
0x7F (127)
1 to 16
1
- - - - 27001 uint
RWES
[`Si;A]
[ Si.A]
Logic (1 to 16)
Source Instance A
Set the instance of the
function selected above.
1 to 250 1 4646
[offset 80]
0x7F (127)
1 to 16
9
- - - - 27009 uint
RWES
Note: Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.