Watlow MLS Manuel d'utilisateur Page 118

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 142
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 117
106 MLS Users Guide
Tuning and Control
General PID Constants
This section gives general PID constants.
Proportional Band Only (P)
Set the PB to 7% of the setpoint
Example
: Setpoint = 450, set the Proportional Band to 31.
Proportional with Integral (PI)
Set the PB to 10% of setpoint.
Example
: Setpoint = 450, set PB to 45.
Set TI to 60.
Set TD to Off.
Set the Output Filter to 2.
PI with Derivative (PID)
Set the PB to 10% of the SP.
Set the TI to 60.
Set the TD to 15% of the TI.
Example
: TI = 60, so TD = 9).
Set the Output Filter to 2.
PB TI TD FIL OUTPUT CT Action
Electric heat with solid state
relays
50 60 15 4 TP 3 Reverse
Electric heat with mechani-
cal relays
50 60 15 6 TP 20 Reverse
Gas heat with motorized
values
60 120 25 8 DZC/DAC NA Reverse
Gas heat with motorized val-
ues (SP > 1200
°
F)
100 240 40 8 DZC/DAC NA Reverse
Extruders with cooling, Heat
with SSRs
50 300 90 8 TP 3 Reverse
Spread set to zero, cool with
solenoid valve
10 OFF OFF 4 TP 20 Direct
Cool with fans 10 OFF OFF 4 TP 60 Direct
Electric heat with open heat
coils
30 20 OFF 4 DZC NA Reverse
Electric heat with SCR con-
trollers
60 60 15 4 DZC/DAC NA Reverse
Vue de la page 117
1 2 ... 113 114 115 116 117 118 119 120 121 122 123 ... 141 142

Commentaires sur ces manuels

Pas de commentaire