Parameters
=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.3
ON
System Group – Setup
Units Type
• Select US or SI units of measurement.
• Read/write
• Modbus: 900
Range
0: US (reciprocate integral term)
1: SI (reciprocate integral term)
Default
0: US
Active
always
Affects
Propband, Integral and Reset (PID Group)
converts Reset and Integral (changes span to degrees or vice
versa)
C or F
• Select the temperature scale for the input.
• Read/write
• Modbus: 901
Range
0: F (Fahrenheit)
1: C (Celsius)
Default
0: F
Active
always
Decimal Point
• Sets the position of the decimal point for input readings.
• Read/write
• Modbus: 606
Range
0: decimal 0000 (for thermocouple and RTD)
1: decimal 000.0 (for for thermocouple and RTD)
Default
0
Active
if Sensor Type (Input Group) is set to RTD or thermocouple
System Group continued